(1) A discharger must ensure that inflow and infiltration does not occur such that the maximum average daily flow exceeds 2 times the ADWF at the treatment plant during storm or snowmelt events with a less than 5-year return period, unless
(a) for municipal wastewater collection systems for which the contributory population to the treatment plant is 10 000 persons or more, the person responsible for the municipal wastewater collection system addresses, as part of a liquid waste management plan, how inflow and infiltration can be reduced, or
(b) if paragraph (a) does not apply, the person responsible for the municipal wastewater collection system
(i) develops a liquid waste management plan or conducts a study, and
(ii) develops and implements measures to reduce inflow and infiltration.
(2) Despite subsection (1), if reductions below 2 times the ADWF are not possible or cost effective based on a cost-benefit analysis, the discharger must
(a) provide full secondary treatment for the entire flow at all times, or
(b) undertake to do all of the things listed in section 43 (2) (a) to (e) [use of storage or conveyance facilities].