Municipal Wastewater Regulation, B.C. Reg. 87/2012

Section 43

Use of storage or conveyance facilities

Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 43 · last amended October 27, 2025 · read from BC Laws on November 17, 2026

The text

(1) A discharger may not use storage or conveyance facilities to reduce (a) the amount of sewer separation required, or (b) the amount of inflow and infiltration reduction required unless the facilities immediately reduce and ultimately prevent the occurrence of combined sewer overflows. (2) If facilities are used under subsection (1) and primary and secondary treatment is available, the discharger must do all of the following: (a) provide at least primary treatment for flows greater than 2 times the ADWF; (b) use the full secondary capacity of the treatment system; (c) combine the primary and secondary municipal effluent prior to discharge; (d) maintain a minimum receiving environment-to-discharge dilution ratio of 40:1; (e) if disinfection is required, provide adequate excess disinfection capacity to ensure disinfection of the entire discharge flow.
Read the Municipal Wastewater Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.