Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 20.21
Application drawings and supplementary instructions for flyforms
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 20.21 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) Application drawings for flyforms must be detailed to show
(a) a plan view, a longitudinal section and a cross-section for each type of flyform panel, and
(b) the weight, calculated position of the centre of gravity and the position of the pickup points for each type of flyform panel.
(2) The design on the application drawings and any supplementary instructions for a flyform panel must provide that, as soon as the panel is landed on a supporting surface, before anyone climbs or walks on the panel and before placement of concrete or reinforcing steel on the panel, the panel must
(a) be able to resist a minimum horizontal load of 3.6 kN (800 lbs) applied in any direction on the top edge,
(b) have a minimum safety factor against overturning about any possible axis of
(i) 1.6 when dead load plus most severe live load configuration plus horizontal loads are considered, and
(ii) 2.0 when dead load plus most severe live load configuration or dead load plus horizontal loads are considered,
(c) have a minimum safety factor of 1.5 against the panel sliding against the supporting surface, and
(d) have flyform legs placed as necessary to attain the required safety factor against overturning.
(3) If any of the requirements of subsection (2) cannot be met for a panel, the employer must ensure that the panel, before being unhooked from the crane or hoist, is secured to the permanent structure or an adjacent panel in a manner specified by the designer of the formwork.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.