An individual is not required to hold a certificate of qualification to operate any of the following:
(a) a power plant not exceeding 10 m2 of boiler capacity;
(b) a steam heating plant not exceeding 30 m2 of boiler capacity;
(c) a fluid heating plant not exceeding 150 m2 of boiler capacity;
(d) a low pressure thermal fluid plant not exceeding 150 m2 of boiler capacity;
(e) a low temperature, low pressure fluid plant not exceeding 300 m2 of boiler capacity;
(f) an unfired plant not exceeding 150 m2 of boiler capacity;
(g) an indirect refrigeration plant, as defined in CSA B52, using refrigerant R 11 and all other refrigeration plants with refrigerant groups A1, A2L, A2 or B1, as defined in CSA B52, not exceeding a total plant capacity of 200 kW prime mover nameplate rating;
(h) a refrigeration plant with refrigerant groups A3, B2L, B2 or B3, as defined in CSA B52, not exceeding a total plant capacity of 50 kW prime mover nameplate rating;
(i) an electric boiler that consumes 100 kW or less in a power plant;
(j) a process
(i) in a petroleum refinery other than in a power plant that is part of the petroleum refinery, and
(ii) if the heat for the process is generated as a result of a reaction that is part of the process or burning;
(k) a pressure vessel plant;
(l) a low pressure thermal fluid plant with a boiler capacity greater than 150 m2 if the plant is equipped with an automated control system that
(i) monitors performance of the plant, including all systems related to automated operation, and automatically alters the operation of the plant to ensure it is operating safely, including during start up and shut down operations,
(ii) is designed so that any failure of the automated control system will cause the plant to go to a predetermined safe state, and
(iii) has been registered by a provincial safety manager in accordance with section 84.1.
Read the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation on BC Laws ↗
Made under Safety Standards Act, SBC 2003, c. 39.