(1) For each test run, the measurements of the concentration of NOx, expressed in ppmvd, and the concentration of O2, expressed as a percentage determined by volume on a dry basis, in the boiler’s or heater’s flue gas must be made simultaneously and in accordance with either (a) the following EPA methods: (i) [Repealed, SOR/2025-229, s. 10] (ii) for the concentration of NOx, EPA Method 7E, and (iii) for the concentration of O2, EPA Method 3A; or (b) ASTM D6522-11 and, for the location of the sampling port and its traverse points, EPA Method 1 or EPA Method 1A, as applicable. (2) Despite subsection (1), the location of the sampling port and its traverse points may be determined for the purpose of that subsection in accordance with EC Method A.