Multi-Sector Air Pollutants Regulations, SOR/2016-151
Section 27
Three test runs
Cite as Multi-Sector Air Pollutants Regulations, SOR/2016-151, s. 27 · current to January 19, 2026 · regulation last amended January 1, 2026
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) A stack test consists of three consecutive test runs conducted within a period of 48 hours, each of which lasts at least 30 minutes and results in a determination of the boiler’s or heater’s NOx emission intensity.
(1.1) However, if conducting a test run that lasts 30 minutes would not be both safe and technically feasible without risking damage to equipment, each test run must last as long as is safe and technically feasible without risking damage to equipment.
(2) The test runs must be conducted while the boiler or heater meets the following conditions:
(a) it is operating with at least 50% of the input energy in its combustion chamber resulting from the introduction of gaseous fossil fuel;
(b) it is operating at at least 60% of its rated capacity or, if such operation would not be both safe and technically feasible without risking damage to equipment, at the highest percentage of its rated capacity that is safe and technically feasible without risking damage to equipment;
(c) it is operating at a steady state;
(d) it is operating with preheated air, if it is equipped to preheat air; and
(e) the same type of gaseous fossil fuel — natural gas or alternative gas — is introduced into its combustion chamber.
Read the Multi-Sector Air Pollutants Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.