fire code, O. Reg. 213/07
Section 9.9.4.14
Cite as fire code, O. Reg. 213/07, s. 9.9.4.14 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A voice communication system shall be provided in each building where the vertical distance between the floor of the top storey and grade exceeds 36 m.
(2) The voice communication system required by Sentence (1) shall
(a) consist of loudspeakers operated from the central alarm and control facility or other location that is accessible to the fire department and supervisory staff appointed under Section 2.8 and that is approved,
(b) provide a clear verbal signal throughout the building, except for elevator cars, and
(c) provide for automatic silencing of the fire alarm signals or alert signals when the loudspeakers are in use.
(3) Approved existing public address systems compatible with the fire safety plan required under Section 2.8 and capable of communicating instructions to the building occupants are deemed to be in compliance with Sentences (1) and (2).
Subsection 9.9.5. Suppression
Access for fire fighting
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.