fire code, O. Reg. 213/07
Section 9.9.4.13
Cite as fire code, O. Reg. 213/07, s. 9.9.4.13 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Smoke alarms shall be installed in each guest suite.
(2) Smoke alarms shall meet the requirements of
(a) CAN/ULC-S531, “Standard for Smoke Alarms”, and
(b) CAN/ULC-S553, “Standard for the Installation of Smoke-Alarms”.
(3) Smoke alarms shall be installed with permanent connections to an electrical circuit and shall have no disconnect switches between the overcurrent device and the smoke alarm.
(4) Despite Sentence (3), battery-operated smoke alarms may be used.
(5) Unless otherwise approved, at least one smoke alarm shall be installed on each floor of a multi-level guest suite and the smoke alarms shall be interconnected so that the actuation of one smoke alarm will cause all smoke alarms within the guest suite to sound.
Voice communication systems
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.