fire code, O. Reg. 213/07

Section 9.9.2.9

Cite as fire code, O. Reg. 213/07, s. 9.9.2.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Fire separations having a fire-resistance rating not less than 45 min shall be provided between major occupancies. (2) Existing fire separations having a fire-resistance rating not less than 30 min are deemed to comply with Sentence (1) if (a) the floor area is sprinklered, or (b) the part of the building containing the major occupancy is equipped with fire detectors and connecting corridors are equipped with smoke detectors as part of the fire alarm system of the building. Protection of openings in fire separations
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.