fire code, O. Reg. 213/07
Section 9.9.2.10
Cite as fire code, O. Reg. 213/07, s. 9.9.2.10 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Closures in fire separations shall be in conformance with
(a) Sentences 3.1.8.4.(2) and 3.1.8.10.(1) of the 1994 Building Code, and
(b) Articles 3.1.8.11. and 3.1.8.13. of the 1994 Building Code.
(2) Despite Sentence (1), openings in fire separations to which Article 9.9.2.8. or 9.9.2.11. applies may be protected with closures having a fire-protection rating not less than 20 min.
(3) If a fire-protection rating of 1 h or less is required, existing closures are deemed to comply with Sentence (1) if they consist of
(a) hollow metal or kalamein doors in hollow metal frames, with openings, if any, protected by wired glass and equipped with self-closing and latching devices, or
(b) wired glass screens set in fixed steel frames.
(4) Where a 20 min fire-protection rating is required, existing closures consisting of door assemblies of 45 mm solid core wood doors installed in solid wood or hollow metal frames and equipped with self-closing and latching devices are deemed to be in compliance with Sentences (1) and (2).
(5) Despite Sentence (1), existing closures in fire separations to which Articles 9.9.2.8. and 9.9.3.6. apply need not be equipped with latching devices in buildings that are not more than 6 storeys in building height.
(6) Where the floor area is sprinklered, existing closures in fire separations to which Article 9.9.2.8. applies are deemed to be in compliance with Clause (1)(a) and Sentence (2).
(7) Fire dampers shall be installed in fire separations in conformance with Article 3.1.8.7. of the 1994 Building Code.
(8) Despite Sentence (7), fire dampers are not required in existing noncombustible ducts at penetrations of fire separations.
Laundry rooms, storage rooms and maintenance shops
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.