fire code, O. Reg. 213/07

Section 9.9.2.8

Cite as fire code, O. Reg. 213/07, s. 9.9.2.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Guest suites shall be separated from adjacent rooms and areas on the same floor area by (a) a fire separation having a fire-resistance rating not less than 30 min in buildings that are not more than 6 storeys in building height, and (b) a fire separation having a fire-resistance rating not less than 45 min in buildings that are more than 6 storeys in building height. Fire separation of corridors (2) Corridors serving guest suites shall be separated from adjacent rooms and areas on the same floor area by (a) a fire separation having a fire-resistance rating not less than 30 min in buildings that are not more than 6 storeys in building height, and (b) a fire separation having a fire-resistance rating not less than 45 min in buildings that are more than 6 storeys in building height. (3) Existing fire separations are deemed to comply with Sentences (1) and (2) if the floor area is sprinklered. Fire separations between major occupancies
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.