fire code, O. Reg. 213/07

Section 9.9.2.7

Cite as fire code, O. Reg. 213/07, s. 9.9.2.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Despite Sentence 9.9.2.1.(6), a floor assembly may be penetrated by an unprotected opening between 2 contiguous storeys up to the fifth storey where (a) the building is of noncombustible construction, (b) the interconnected floor space does not contain sleeping accommodation, and (c) the required fire-resistance rating of the floor assembly is maintained. (2) Despite Sentence 9.9.2.1.(6), in a building that is not more than 3 storeys in building height and not more than 600 m2 in building area, a floor assembly is not required to be constructed as a fire separation between 2 contiguous storeys where (a) the interconnected floor space consists of the first storey and the storey next above or below, but not both, (b) the interconnected floor space is sprinklered, and (c) the sprinkler system is equipped with a water flow device and electrical supervision in conformance with Sentence 3.2.8.7.(2) of the 1994 Building Code. (3) Despite Sentence 9.9.2.1.(6), a floor assembly in a storage garage does not need to be a fire separation. (4) Interconnected floor spaces in conformance with Subsection 3.2.8. of the 1994 Building Code are deemed to be in compliance with Sentence (1). Fire separation of guest suites