fire code, O. Reg. 213/07

Section 9.9.2.3

Cite as fire code, O. Reg. 213/07, s. 9.9.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings to which Sentence 9.9.2.2.(1) does not apply and that are not more than 4 storeys in building height shall comply with Sentences (2) and (3). (2) Floor assemblies and walls, columns and arches supporting floor assemblies shall have a fire-resistance rating not less than 45 min. (3) Smoke detectors shall be provided in corridors serving guest suites in buildings of combustible construction. (4) A building that is sprinklered is deemed to be in compliance with Sentences (2) and (3). Buildings over 4 storeys but not more than 6 storeys
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.