fire code, O. Reg. 213/07

Section 9.9.2.4

Cite as fire code, O. Reg. 213/07, s. 9.9.2.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings to which Articles 9.9.2.2. and 9.9.2.3. do not apply and that are not more than 6 storeys in building height shall (a) have a fire-resistance rating not less than 45 min for floor assemblies and walls, columns and arches supporting floor assemblies, and (b) be sprinklered, where the building is of combustible construction. (2) Where only the roof assembly is of combustible construction, the building is deemed to be in compliance with Clause (1)(b) where (a) the ceiling membrane has a fire-resistance rating not less than 45 min and the attic space is fire stopped in accordance with Article 3.1.11.5. of the 1994 Building Code, (b) the roof assembly is of heavy timber construction in conformance with Article 3.1.4.6. of the 1994 Building Code, or (c) the top storey and attic space are sprinklered. (3) Where smoke detectors are provided in corridors serving guest suites, a building of heavy timber construction conforming to Article 3.1.4.6. of the 1994 Building Code is deemed to be in compliance with Sentence (1). Buildings over 6 storeys
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.