fire code, O. Reg. 213/07

Section 9.8.3.3

Cite as fire code, O. Reg. 213/07, s. 9.8.3.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Each residential unit shall have direct access to at least one means of escape that may be shared if (a) the means of escape is separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 30 min, (b) the flame-spread rating of interior wall and ceiling finishes within the means of escape does not exceed 150, and (c) the means of escape does not involve entering another residential unit or other occupancy and leads directly to the exterior with direct access to ground level. (2) Where a means of escape provided by Sentence (1) serves a residential unit situated entirely on the third storey, the detached house, semi-detached house or row house shall be equipped with interconnected smoke alarms conforming to Article 9.8.4.1. Two means of escape