fire code, O. Reg. 213/07
Section 9.8.3.4
Cite as fire code, O. Reg. 213/07, s. 9.8.3.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Each residential unit shall be served by at least two means of escape arranged in such a manner that
(a) one means of escape shall be through a door which may lead through another residential unit, and
(b) the second means of escape shall be through a window if
(i) the window conforms to Sentence (2) or (3), and
(ii) the detached house, semi-detached house or row house is equipped with interconnected smoke alarms conforming to Article 9.8.4.1.
(2) A window may serve as a second means of escape if
(a) the sill is not more than 1 m above or below the adjacent ground level,
(b) the window can be opened from the inside without the use of tools,
(c) the window has an individual, unobstructed open portion having a minimum area of 0.38 m2 with no dimension less than 460 mm,
(d) the sill height does not exceed 900 mm above the floor or fixed steps,
(e) where the window has a window-well, a clearance of at least 1 m is provided in the window-well in front of the window, and
(f) where the window has a window-well, the window opens into the residential unit and does not interfere with escape.
(3) A window may serve as a second means of escape if
(a) the window is of a casement type,
(b) the window is not less than 1060 mm high and 560 mm wide,
(c) the sill of the window is not more than 900 mm above the inside floor, and
(d) the sill of the window is not less than 1 m and not more than 5 m above the adjacent ground level.
Existing means of escape with sprinklers
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.