fire code, O. Reg. 213/07

Section 9.4.2.3

Cite as fire code, O. Reg. 213/07, s. 9.4.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings of combustible construction shall comply with the provisions of Sentences (2) and (3) where the building is (a) not more than 1 storey in building height and not greater than 2400 m2 in building area, (b) not more than 2 storeys in building height and not greater than 1600 m2 in building area, or (c) not more than 4 storeys in building height and not greater than 500 m2 in building area. (2) Floor assemblies and walls, columns and arches supporting floor assemblies shall have a fire-resistance rating not less than 45 min. (3) Despite Sentence 9.4.4.2.(2), smoke detectors shall be provided in bedrooms, corridors, lounges and sitting areas. (4) A building that is sprinklered is deemed to be in compliance with Sentences (2) and (3). All other buildings
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.