fire code, O. Reg. 213/07

Section 9.4.2.2

Cite as fire code, O. Reg. 213/07, s. 9.4.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings of combustible construction shall comply with the provisions of Sentence (2) where the building is (a) 1 storey in building height and not greater than 1000 m2 in building area, or (b) 2 storeys in building height and not greater than 500 m2 in building area. (2) Floor assemblies and walls, columns and arches supporting floor assemblies shall have a fire-resistance rating not less than 45 min. (3) Despite Sentence (2), where the building is sprinklered, a fire-resistance rating is not required for floor assemblies or for walls, columns and arches supporting floor assemblies. Combustible construction up to 4 storeys
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.