fire code, O. Reg. 213/07
Section 9.4.2.4
Cite as fire code, O. Reg. 213/07, s. 9.4.2.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Buildings not described in Articles 9.4.2.2. and 9.4.2.3. shall
(a) have a fire-resistance rating not less than 45 min for floor assemblies and walls, columns and arches supporting floor assemblies, and
(b) be sprinklered, where the building is of combustible construction.
(2) If only the roof assembly of a building is of combustible construction, the building is deemed to comply with Clause (1)(b) if
(a) the top storey and attic space are sprinklered, or
(b) the ceiling membrane has a fire-resistance rating not less than 45 min and the attic space is fire stopped in accordance with Article 3.1.9.3. of the 1986 Building Code.
Fire separations between occupancies
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.