fire code, O. Reg. 213/07
Section 9.4.2.1
Cite as fire code, O. Reg. 213/07, s. 9.4.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Fire separations required under this Section to have a fire-resistance rating shall comply with Subsection 3.1.5. and Articles 3.1.6.1., 3.1.6.2. and 3.1.6.3. of the 1986 Building Code.
(2) If a fire-resistance rating of 1 h or less is required, existing wall assemblies, floor assemblies and ceilings and their supporting assemblies are deemed to comply with Sentence (1) if they consist of lath and plaster or gypsum board.
(3) Heavy timber construction that complies with Article 3.1.4.4. of the 1986 Building Code is deemed to have a 45 min fire-resistance rating.
(4) Buildings with limited combustible components may be approved as noncombustible construction.
(5) Floor assemblies shall be constructed as fire separations with fire-resistance ratings in accordance with this Subsection.
Combustible construction up to 2 storeys
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.