fire code, O. Reg. 213/07
Section 9.2.2.2
Cite as fire code, O. Reg. 213/07, s. 9.2.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Closures that are in compliance with Sentences 3.1.6.4.(2) and 3.1.6.7.(1) of the 1986 Building Code shall be provided in fire separations.
(2) Where Sentence (1) requires
(a) a 1 h or a 45 min fire-protection rating, existing hollow metal or kalamein doors, with or without wired glass and equipped with self-closing devices, and existing hollow metal frames are deemed to be in compliance,
(b) a 1 h or a 45 min fire-protection rating, existing wired glass screens set in fixed steel frames are deemed to be in compliance, or
(c) a 20 min fire-protection rating, existing 45 mm solid core wood doors and existing solid wood frames are deemed to be in compliance.
(3) Despite the requirements referred to in Sentence (1), fire dampers or fire stop flaps are not required to be installed in existing noncombustible ducts at penetrations of a fire separation.
Fire separations for hazardous areas
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.