fire code, O. Reg. 213/07
Section 9.2.2.3
Cite as fire code, O. Reg. 213/07, s. 9.2.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) In high buildings classified in the 1986 Building Code under Subsection 3.2.6., fire separations that are in compliance with Subsection 3.5.2. of the 1986 Building Code shall be provided between service rooms and assembly occupancies.
(2) In buildings not referred to in Sentence (1), fire separations that are in compliance with Subsection 3.5.2. of the 1986 Building Code shall be provided between service rooms and assembly occupancies.
(3) A fire separation having a fire-resistance rating not less than 30 minutes is deemed to comply with Sentence (2) if
(a) the service room is sprinklered, or
(b) a detection system is provided and connected to the building fire alarm system.
(4) Fire separations shall be provided between theatrical stages and assembly occupancies in compliance with Sentences 3.3.2.14.(3) to (5) of the 1986 Building Code.
(5) Despite Sentence (4), existing fire separations may be approved.
Interior finishes
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.