fire code, O. Reg. 213/07

Section 9.2.2.1

Cite as fire code, O. Reg. 213/07, s. 9.2.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Fire separations shall be provided between assembly occupancies described in Subsection 9.2.1. and other major occupancies in compliance with Article 3.1.3.2. of the 1986 Building Code. (2) If Sentence (1) requires a fire separation having a 2 h fire-resistance rating, a fire separation having a fire-resistance rating not less than 1 h is deemed to comply with Sentence (1) if (a) the building is sprinklered with a sprinkler system that complies with Article 9.2.5.2., or (b) the building has a detection system that is connected to the building fire alarm system. (3) If Sentence (1) requires a fire separation having a 1 h fire-resistance rating, a fire separation having a fire-resistance rating not less than 30 minutes is deemed to comply with Sentence (1) if (a) the building is sprinklered with a sprinkler system that complies with Article 9.2.5.2., or (b) the building has a detection system that is connected to the building fire alarm system. Protection of openings in fire separations
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.