fire code, O. Reg. 213/07
Section 6.4.3.7
Cite as fire code, O. Reg. 213/07, s. 6.4.3.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The dry portion of the fire department connection piping of a standpipe system shall be hydrostatically tested at a pressure of not less than 1050 kPa (gauge) for 2 hours at intervals of not more than five years where
(a) the fire department connection piping has been in service for more than thirty years, or
(b) the age of the fire department connection piping cannot be determined.
(2) Despite Sentence (1), if, on July 1, 2018, fire department connection piping has not been hydrostatically tested within the previous five years, the first test required by Sentence (1) shall be completed before January 1, 2019.
(3) Fire department connection piping shall be inspected annually with any plugs or caps removed to ensure that
(a) the fire department connection is physically unobstructed and readily accessible,
(b) the fire department connection identification sign is in place and visible,
(c) the fire department connection is free of wear, rust or obstruction,
(d) couplings or swivels are not damaged and rotate smoothly,
(e) gaskets are in place and in good condition,
(f) the check valve is not leaking,
(g) the automatic drain valve is in place and operating properly, and
(h) fire department connection clappers are in place and operating properly.
(4) The annual inspection referenced in Sentence (3) shall be recorded and kept in accordance with Subsection 1.1.2.