fire code, O. Reg. 213/07

Section 6.4.3.8

Cite as fire code, O. Reg. 213/07, s. 6.4.3.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

In buildings containing a hotel, flow and pressure tests shall be conducted annually at the highest and most remote hose valve or hose connection to verify that the water supply for the standpipe system is provided as originally designed. SECTION 6.5 SPRINKLER SYSTEMS Subsection 6.5.1. General Repair, replacement, alterations, inspection, testing and maintenance
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.