fire code, O. Reg. 213/07

Section 6.4.3.6

Cite as fire code, O. Reg. 213/07, s. 6.4.3.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Standpipe system piping which normally remains dry shall be hydrostatically tested in accordance with Article 6.4.3.2. at intervals of not more than five years. (2) Water supply pressure and system air pressure for automatic dry standpipe systems shall be checked weekly by using gauges to ensure that the system is maintained at the required operating pressure. Fire department connections
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.