fire code, O. Reg. 213/07
Section 5.6.2.3
Cite as fire code, O. Reg. 213/07, s. 5.6.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Cylinders containing compressed gas and located outdoors shall be
(a) at least 1.5 m from any building opening if the aggregate capacity of expanded gas is not more than 170 m3,
(b) at least 7.5 m from any building opening if the aggregate capacity of expanded gas is over 170 m3 but not more than 500 m3, or
(c) at least 15 m from any building opening if the aggregate capacity of expanded gas is over 500 m3.
(2) Sentence (1) does not apply if the building opening is into a room that conforms to Sentence 5.6.2.4.(1).
Indoor storage of flammable compressed gases
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.