fire code, O. Reg. 213/07

Section 5.6.2.2

Cite as fire code, O. Reg. 213/07, s. 5.6.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Fencing required in Article 5.6.2.1. shall be (a) firmly anchored and substantially constructed, (b) designed to discourage climbing, (c) not less than 1.8 m high, (d) provided with gates that shall be locked when the storage area is not staffed, and (e) kept clear of obstructions so that gates may be fully opened at all times. (2) An outdoor storage area that exceeds 100 m2 and is used for storage of cylinders containing compressed gas shall be arranged such that there is a clear space of not less than (a) 30 m between stored products and brush or forested areas, and (b) 6 m between stored products and uncontrolled grass or weeds. Clearances from building openings
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.