fire code, O. Reg. 213/07
Section 5.6.2.4
Cite as fire code, O. Reg. 213/07, s. 5.6.2.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentences (2), (3) and (5), cylinders containing flammable compressed gas stored indoors shall be located in a room that
(a) is separated from the remainder of the building by a gas-tight fire separation having a fire-resistance rating not less than 2 h,
(b) is located on an exterior wall of the building,
(c) can be entered from the exterior,
(d) has all closures that lead into the interior of the building
(i) equipped with self-closing devices in such a manner that the closures are kept closed when not in use, and
(ii) constructed so as to prevent migration of gases from the room into other parts of the building,
(e) is constructed so that an exterior wall provides explosion venting
(i) in the ratio of 0.2 m2 for each cubic metre of room volume, or
(ii) in the ratio computed in accordance with NFPA 68, “Standard on Explosion Protection by Deflagration Venting”, except in no case less than 650 cm2 of vent area for each cubic metre of room volume,
(f) has ventilation that complies with Sentence (4),
(g) does not contain fuel-fired equipment or high temperature heating elements, and
(h) is used for no purpose other than the storage of compressed gas.
(2) Cylinders of flammable, lighter than air compressed gas are permitted to be stored outside of a room described in Sentence (1) provided that the aggregate capacity per fire compartment of expanded gas outside of the room is not more than,
(a) 60 m3 in a building of combustible construction that is not sprinklered, and
(b) 170 m3 in a sprinklered building or in a building of noncombustible construction.
(3) Cylinders of flammable compressed gas which are heavier than air may be stored in rooms other than those described in Sentence (1) if they are stored in a fire compartment having a fire-resistance rating of at least 45 min and
(a) the aggregate capacity does not exceed 100 kg,
(b) the number of cylinders does not exceed three,
(c) the cylinders are not located in the basement or other areas below grade, and
(d) the fire compartment has ventilation conforming to Sentence (4).
(4) The ventilation required by Clauses (1)(f) and (3)(d) shall be
(a) mechanical ventilation to the outside that ensures at least one air change per hour, or
(b) natural ventilation to the outside through non-closeable louvred openings with
(i) at least one opening no more than 0.3 m from the ceiling and one opening no more than 0.3 m from the floor,
(ii) all openings at ceiling level having an aggregate free opening area of at least 0.2 m2 per 100 m2 of the floor area,
(iii) all openings at floor level having an aggregate free opening area of at least 0.2 m2 per 100 m2 of the floor area, and
(iv) the openings located to ensure cross ventilation.
(5) “Single trip” non-refillable cylinders with water capacities of more than 375 g and less than 1.13 kg located within mercantile occupancies shall conform to the provisions stipulated in Ontario Regulation 211/01 (Propane Storage and Handling) made under the Technical Standards and Safety Act, 2000.
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.