fire code, O. Reg. 213/07
Section 5.5.4.2
Cite as fire code, O. Reg. 213/07, s. 5.5.4.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The use of dangerous goods in a laboratory shall be confined inside a power-ventilated enclosure conforming to Articles 5.5.4.3. and 5.5.4.4. when
(a) their use releases flammable vapours or causes runaway or potentially explosive reactions,
(b) liquids are heated to a temperature equal to or greater than their flash point, or
(c) Class I liquids or unstable liquids are used.
(2) A power-ventilated enclosure required in Sentence (1) shall not be used for the storage of dangerous goods and any quantity in excess of the supply necessary for normal operations shall conform to Subsection 5.5.5.
Enclosure exhaust ventilation
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.