(1) The ventilation system for a power-ventilated enclosure required in Article 5.5.4.2. shall
(a) conform to NFPA 91, “Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids”,
(b) provide continuous exhaust ventilation at an air velocity sufficient to prevent the accumulation of combustible or reactive deposits in the power-ventilated enclosure and its exhaust duct system,
(c) confine dangerous goods vapours and particles to the area where they are generated and exhaust them to the outdoors,
(d) not return the exhausted air to the building, and
(e) be provided with well identified control switches that are
(i) located outside of the power-ventilated enclosure, and
(ii) readily accessible in case of an emergency.
(2) The ventilation system described in Sentence (1) shall not be interlocked with a fire detection, fire alarm or make-up air system.
(3) Where combustible or reactive deposits can accumulate in the power-ventilated enclosure and its exhaust duct system and create a fire or explosion hazard
(a) provisions shall be made to remove such deposits so they do not create a fire or explosion hazard, or
(b) an automatic fire suppression system shall be provided in conformance with an applicable standard set out in Article 2.1.3.5.