fire code, O. Reg. 213/07
Section 5.5.4.1
Cite as fire code, O. Reg. 213/07, s. 5.5.4.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A laboratory shall be provided with continuous mechanical ventilation designed to ensure that dangerous goods vapours and particles
(a) do not accumulate in the laboratory,
(b) are prevented from migrating to other parts of the building,
(c) do not accumulate in the ventilation system,
(d) are exhausted to the outdoors, and
(e) are not returned to the building.
(2) A ventilation system required in Sentence (1) shall be provided with monitoring devices to
(a) indicate that the ventilation system is in operation, and
(b) sound an alarm if the ventilation system is malfunctioning.
(3) A ventilation system required in Sentence (1) shall be maintained to ensure it fulfils the function for which it was designed.
Power-ventilated enclosure
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.