fire code, O. Reg. 213/07
Section 5.5.3.6
Cite as fire code, O. Reg. 213/07, s. 5.5.3.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Electrical equipment, mechanical systems, piping, valves and automatic and manual control and safety devices shall be inspected at intervals not greater than 12 months and maintained in good operating condition at all times.
(2) The ventilation systems serving a laboratory shall be inspected and cleaned to prevent the accumulation of combustible or reactive deposits and the intervals between inspections shall be not greater than
(a) 12 months for the ventilation systems of the laboratory and dangerous goods storage areas, and
(b) six months for the ventilation system of a power-ventilated enclosure required in Article 5.5.4.2.
Subsection 5.5.4. Ventilation
General ventilation
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.