fire code, O. Reg. 213/07

Section 4.5.7.1

Cite as fire code, O. Reg. 213/07, s. 4.5.7.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentences (2) and (3), valves in piping systems for flammable liquids or combustible liquids shall be designed to accommodate the temperatures and pressures of those systems and shall conform to ULC/ORD-C842, “Guide for the Investigation of Valves for Flammable and Combustible Liquids”. (2) Every hose nozzle valve shall conform to CAN/ULC-S620, “Standard for Hose Nozzle Valves for Flammable and Combustible Liquids”. (3) Every emergency valve shall conform to CAN/ULC-S651, “Standard for Emergency Valves for Flammable and Combustible Liquids”. (4) Valves that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentences (1), (2) and (3) if the valves are not leaking and are constructed of material that is in conformance with Article 4.5.2.1. Shut-off valves
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.