fire code, O. Reg. 213/07
Section 4.5.6.14
Cite as fire code, O. Reg. 213/07, s. 4.5.6.14 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) In the design of piping systems for flammable liquids or combustible liquids, provision shall be made for the expansion and contraction of the piping system and of the product it conveys.
(2) To prevent excessive stresses resulting from vibration, settling or temperature changes
(a) flexible non-metallic hose connectors conforming to CAN/ULC-S633, “Standard for Flexible Connector Piping for Fuels Connectors for Flammable and Combustible Liquids”, are permitted to be used where necessary in underground piping systems carrying flammable liquids or combustible liquids,
(b) flexible metallic and non-metallic pipe and fittings conforming to CAN/ULC-S679, “Standard for Metallic and Nonmetallic Underground Piping for Flammable and Combustible Liquids”, are permitted to be used where necessary in underground piping systems carrying flammable liquids or combustible liquids, or
(c) flexible metallic hose connectors conforming to ULC/ORD-C536, “Flexible Metallic Hose”, are permitted to be used where necessary in aboveground and underground piping systems carrying flammable liquids or combustible liquids.
Subsection 4.5.7. Valves in Piping Systems
Design
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.