fire code, O. Reg. 213/07
Section 4.5.7.2
Cite as fire code, O. Reg. 213/07, s. 4.5.7.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Shut-off valves shall be provided in all flammable liquid or combustible liquid piping and pumping systems.
(2) Where practicable, valves referred to in Sentence (1) shall be located outdoors or be immediately accessible from outdoors.
(3) Except as permitted in Sentence (4), steel shut-off valves shall be provided
(a) at connections to all aboveground storage tanks,
(b) on supply piping where it enters buildings or structures,
(c) on branch lines from the main supply line,
(d) on supply lines at dispensing locations,
(e) to isolate one part of a piping system from another, and
(f) to isolate meters and air eliminators.
(4) Stainless steel, monel metal or lined steel bodied valves are permitted to be used when special conditions warrant their use.