fire code, O. Reg. 213/07

Section 4.4.3.4

Cite as fire code, O. Reg. 213/07, s. 4.4.3.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Liquid media leak detection testing of piping systems shall conform to Sentences (2) to (9). (2) Test devices and methods shall conform to the performance requirements of ULC/ORD-C107.12, “Line Leak Detection Devices for Flammable Liquid Piping”. (3) Tests shall be conducted by an individual who has been trained in the proper use of the test device and the operating procedures. (4) A sufficient amount of time shall be allocated to stabilize the temperature of the liquid throughout the volume of the piping during the test. (5) Except as provided in Sentences (6) and (7), test pressure shall (a) be the greater of 350 kPa (gauge) or 1.5 times the maximum operating pressure, and (b) not exceed the piping manufacturer’s test specifications. (6) Test pressures exceeding 700 kPa (gauge) shall not be permitted unless the pressure, and piping system is designed for such pressures. (7) Where test pressures exceed the design pressures for pumps or similar components connected to the piping system being tested, such pumps or components shall be isolated from the test procedure. (8) Class I liquids shall not be used for pressure testing piping systems, except that pressure piping normally containing Class I liquids is permitted to be tested with such liquids at pressures not exceeding their maximum operating pressures. (9) The piping system shall be considered to be leaking if the leak rate exceeds 0.38 L/h. Protocols for leak detection testing of sumps
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.