fire code, O. Reg. 213/07

Section 4.4.3.3

Cite as fire code, O. Reg. 213/07, s. 4.4.3.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) A pressure decline test using an inert gas is permitted to be used as a leak detection test for piping systems that (a) are new or in use, and (b) convey a volume of less than 1000 L. (2) A pressure decline test performed on a piping system shall conform to Sentences (3) to (9). (3) The design and installation of the piping system permitting, the piping system’s contents shall be drained prior to conducting the pressure decline test procedure. (4) Pumps, dispensers and other auxiliary equipment that are connected to the piping system and cannot withstand the pressure of the test shall be isolated from the test procedure to prevent damage to the equipment. (5) A stabilization period of up to 30 min is required after pressurization. (6) Pipe volumes of 500 L or less shall be pressurized for at least 60 min after stabilization. (7) Pipe volumes greater than 500 L but less than 1000 L shall be pressurized for at least 2 h after stabilization. (8) Test pressures shall (a) be the greater of 350 kPa (gauge) or 1.5 times the maximum operating pressure, and (b) not exceed the piping manufacturer's test specifications. (9) The piping system shall be considered to be leaking if any pressure decline is detected within the time periods stated. Protocols for liquid media leak detection testing of piping systems
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.