fire code, O. Reg. 213/07

Section 4.4.3.5

Cite as fire code, O. Reg. 213/07, s. 4.4.3.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Static liquid media leak detection testing of turbine, transition, dispenser and pump sumps shall conform to Sentences (2) to (4). (2) Static liquid media testing of sumps shall be performed at the installation stage after all electrical and mechanical work passing through the sump wall has been completed but before any backfilling around the exterior of the sump is completed. (3) The liquid used for the test shall (a) exceed the elevation of the piping and other points of entry into the sump by at least 50 mm, and (b) not be a flammable liquid or a combustible liquid. (4) The minimum duration of the test shall be 1 h with no visual or measured evidence of leakage. Subsection 4.4.4. Leak Detection Monitoring of Storage Tanks and Piping Systems Inventory reconciliation