fire code, O. Reg. 213/07
Section 4.4.3.2
Cite as fire code, O. Reg. 213/07, s. 4.4.3.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Pneumatic leak detection tests using compressed air shall not be performed on storage tanks and piping systems having once contained flammable liquids or combustible liquids.
(2) Except as provided in Sentence (1), pneumatic leak detection tests using compressed air or an inert gas shall include the application of soap and water to the storage tank and piping surface, fittings, joints and connections to help in the detection of leaks.
(3) In the case of underground storage tanks or piping, the test referred to in Sentence (2) shall be conducted prior to covering the tank or piping system.
(4) Where a pneumatic leak detection test is conducted before an underground storage tank is backfilled, in the case of a new tank, or after the tank is uncovered, in the case of a previously installed tank, the test pressure shall be in conformance with the production testing requirements of
(a) CAN/ULC-S603, “Standard for Steel Underground Tanks for Flammable and Combustible Liquids”, or
(b) CAN/ULC-S615, “Standard for Fibre Reinforced Plastic Underground Tanks for Flammable and Combustible Liquids”.
(5) Pneumatic leak detection tests shall not be performed on field-erected aboveground storage tanks.
(6) Measures shall be taken to guard against the hazards associated with pneumatic leak detection testing in areas where explosive mixtures of flammable liquid or combustible liquid vapours and air may be present in the vicinity of a storage tank that has been in use.
Protocols for pneumatic leak detection testing of piping systems