fire code, O. Reg. 213/07
Section 4.4.3.1
Cite as fire code, O. Reg. 213/07, s. 4.4.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Where field test methods are included in the storage tank construction standards referred to in Articles 4.3.1.2. and 4.3.1.3., such tests shall be permitted for storage tanks conforming to those standards.
(2) If a precision leak detection test referred to in Sentence 4.4.2.1.(10) detects a leak rate exceeding 0.38 L/h on an underground storage tank, the tank shall be considered to be leaking.
(3) During a leak detection test on a storage tank, the pressure at the bottom of the tank shall not exceed the tank manufacturer’s specifications.
Pneumatic leak detection tests
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.