fire code, O. Reg. 213/07

Section 4.3.7.4

Cite as fire code, O. Reg. 213/07, s. 4.3.7.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentence (2), no part of a secondary containment wall shall be less than 1.5 m from a storage tank shell. (2) The distance required in Sentence (1) is permitted to be waived, provided the storage tank (a) has a capacity of not more than 50000 L and is constructed in accordance with (i) CAN/ULC-S652, “Standard for Tank Assemblies for the Collection, Storage and Removal of Used Oil”, CAN/ULC-S653, “Aboveground Steel Contained Tank Assemblies for Flammable and Combustible Liquids”, or CAN/ULC-S677, “Standard for Fire Tested Aboveground Tank Assemblies for Flammable and Combustible Liquids”, incorporating secondary containment, or (ii) CAN/ULC-S601, “Shop Fabricated Steel Aboveground Tanks for Flammable and Combustible Liquids”, for double-walled storage tanks, or (b) conforms to ULC-S655, “Aboveground Protected Tank Assemblies for Flammable and Combustible Liquids”. (3) Aboveground storage tanks shall be protected by posts or guardrails where they are exposed to potential collision damage. (4) Secondary containment walls that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentences (1), (2) and (3). Access to storage tanks and ancillary equipment
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.