fire code, O. Reg. 213/07

Section 4.3.7.3

Cite as fire code, O. Reg. 213/07, s. 4.3.7.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as permitted in Sentence (3), a secondary containment for a single storage tank shall have a volumetric capacity of not less than 110% of the capacity of the tank. (2) Except as permitted in Sentence (3), a secondary containment for more than one storage tank shall have a volumetric capacity of not less than the sum of (a) the capacity of the largest storage tank located in the contained space, and (b) 10% of the greater of (i) the capacity specified in Clause (a), or (ii) the aggregate capacity of all other storage tanks located in the contained space. (3) When the secondary containment is designed to prevent the entry of precipitation and water used for firefighting purposes into the contained space, it shall have a volumetric capacity of not less than the capacity of the largest storage tank located in the contained space. Clearances