fire code, O. Reg. 213/07

Section 4.3.7.5

Cite as fire code, O. Reg. 213/07, s. 4.3.7.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) A secondary containment shall permit (a) access to storage tanks, valves and ancillary equipment, (b) egress from the contained space, and (c) access for firefighting as specified in Article 4.3.2.4. (2) Where a storage tank contains Class I liquids, provisions shall be made for the normal operation of valves and for access to the storage tank roof without entering the contained space created by the secondary containment when (a) the average height of the secondary containment exceeds 3.5 m, measured from the ground level of the interior of the contained area, or (b) the distance between the tank shell and the top inside edge of the secondary containment wall is less than the height of this wall. Emergency venting