fire code, O. Reg. 213/07
Section 4.3.7.2
Cite as fire code, O. Reg. 213/07, s. 4.3.7.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The base and walls of a secondary containment shall be made of noncombustible materials, and shall be designed, constructed and maintained to
(a) withstand full hydrostatic head, and
(b) provide a permeability of not more than 10-6 cm/s to the flammable liquids or combustible liquids contained in the storage tanks.
(2) A membrane providing the level of impermeability required in Clause (1)(b) shall
(a) conform to CAN/ULC-S668, “Standard for Liners Used for Secondary Containment of Aboveground Flammable and Combustible Liquid Tanks”, and
(b) be installed in accordance with the manufacturer’s instructions.
(3) A membrane that is installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continues to meet those requirements is deemed to comply with Clause (2)(a).
(4) Except as provided in Sentence (5), openings shall not be permitted in a secondary containment.
(5) Where piping passes through a secondary containment, such passages shall conform to Sentences (1) and (2).
Capacity