fire code, O. Reg. 213/07

Section 4.3.2.3

Cite as fire code, O. Reg. 213/07, s. 4.3.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) The minimum separation between a flammable liquid or combustible liquid storage tank and a liquefied petroleum gas cylinder or tank shall be 6 m. (2) Secondary containments for flammable liquid and combustible liquid storage tanks shall not contain any liquefied petroleum gas cylinder or tank, and the centre line of the secondary containment wall shall be not less than (a) 3 m away from a liquefied petroleum gas cylinder, and (b) 6 m away from a liquefied petroleum gas tank. Fire department access
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.