fire code, O. Reg. 213/07

Section 4.3.2.2

Cite as fire code, O. Reg. 213/07, s. 4.3.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as required in Sentences (2) and (3) and in Article 4.3.2.3., the minimum distance between every combination of two aboveground storage tanks shall be 0.25 times the sum of their diameters, but shall be not less than 1 m. (2) The minimum distance between any two storage tanks, neither of which has a capacity of more than 250000 L, shall be 1 m. (3) Where either of two aboveground storage tanks contains unstable liquids, the distance required in Sentences (1) and (2) shall be doubled. Clearances from liquefied petroleum gas cylinders and tanks
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.