(1) Except as provided in Sentences (2) and (3), storage tanks for flammable liquids or combustible liquids shall be spaced so that each storage tank is accessible for firefighting purposes.
(2) An access route constructed in conformance with Subsection 3.2.5. of Division B of the Building Code shall be provided in outdoor storage areas to permit the approach of fire department vehicles to within 60 m travelling distance of any storage tank.
(3) Where firefighting access to storage tanks containing Class I or II liquids is not provided, fire extinguishing measures conforming to Sentence 4.3.2.5.(2) shall be provided.