fire code, O. Reg. 213/07

Section 4.3.16.1

Cite as fire code, O. Reg. 213/07, s. 4.3.16.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) The removal, abandonment in place, disposal or temporary taking out of service of an underground storage tank shall be in conformance with (a) NFPA 30, “Flammable and Combustible Liquids Code”, (b) API RP 1604, “Closure of Underground Petroleum Storage Tanks”, or (c) CCME PN 1326, “Environmental Code of Practice for Aboveground and Underground Storage Tank Systems Containing Petroleum and Allied Petroleum Products”. (2) Where a storage tank has been out of service for more than 12 months, the tank and piping shall be tested for leakage in conformance with Section 4.4. (3) Underground storage tanks that were abandoned in place or temporarily taken out of service, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentence (1). Removal
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.