fire code, O. Reg. 213/07
Section 4.3.15.2
Cite as fire code, O. Reg. 213/07, s. 4.3.15.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Openings that are independent of the fill pipe and are used for measuring the liquid level in storage tanks containing Class I or II liquids shall be equipped with a vapour-tight cap which shall be opened only when measuring the liquid level.
(2) Openings referred to in Sentence (1) shall be protected against overflow and vapour pressure by means of a spring-loaded check valve.
Subsection 4.3.16. Out of Service
Underground storage tanks
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.